NOTICES
DEPARTMENT OF ENVIRONMENTAL PROTECTION
Applications, Actions and Special Notices
APPLICATIONS
[39 Pa.B. 687]
[Saturday, February 7, 2009]
THE CLEAN STREAMS LAW AND THE FEDERAL CLEAN WATER ACT
APPLICATIONS FOR NATIONAL POLLUTION DISCHARGE ELIMINATION SYSTEM (NPDES) PERMITS AND WATER QUALITY MANAGEMENT (WQM) PERMITS This notice provides information about persons who have applied for a new, amended or renewed NPDES or WQM permit, a permit waiver for certain stormwater discharges or submitted a Notice of Intent (NOI) for coverage under a general permit. The applications concern, but are not limited to, discharges related to industrial, animal or sewage waste, discharges to groundwater, discharges associated with municipal separate storm sewer systems (MS4), stormwater associated with construction activities or concentrated animal feeding operations (CAFOs). This notice is provided in accordance with 25 Pa. Code Chapters 91 and 92 and 40 CFR Part 122, implementing The Clean Streams Law (35 P. S. §§ 691.1--691.1001) and the Federal Clean Water Act.
Location Permit Authority Application Type or Category Section I NPDES Renewals Section II NPDES New or amendment Section III WQM Industrial, sewage or animal waste; discharge into groundwater Section IV NPDES MS4 individual permit Section V NPDES MS4 permit waiver Section VI NPDES Individual permit stormwater construction Section VII NPDES NOI for coverage under NPDES general permits For NPDES renewal applications in Section I, the Department of Environmental Protection (Department) has made a tentative determination to reissue these permits for 5 years subject to effluent limitations and monitoring and reporting requirements in their current permits, with appropriate and necessary updated requirements to reflect new and changed regulations and other requirements.
For applications for new NPDES permits and renewal applications with major changes in Section II, as well as applications for MS4 individual permits and individual stormwater construction permits in Sections IV and VI, the Department, based upon preliminary reviews, has made a tentative determination of proposed effluent limitations and other terms and conditions for the permit applications. These determinations are published as proposed actions for comments prior to taking final actions.
Unless indicated otherwise, the Environmental Protection Agency (EPA) Region III Administrator has waived the right to review or object to proposed NPDES permit actions under the waiver provision in 40 CFR 123.24(d).
Persons wishing to comment on an NPDES application are invited to submit a statement to the regional office noted before an application within 30 days from the date of this public notice. Persons wishing to comment on a WQM permit application are invited to submit a statement to the regional office noted before the application within 15 days from the date of this public notice. Comments received within the respective comment periods will be considered in the final determinations regarding the applications. Comments should include the name, address and telephone number of the writer and a concise statement to inform the Department of the exact basis of a comment and the relevant facts upon which it is based.
The Department will also accept requests for a public hearing on applications. A public hearing may be held if the responsible office considers the public response significant. If a hearing is scheduled, a notice of the hearing will be published in the Pennsylvania Bulletin and a newspaper of general circulation within the relevant geographical area. The Department will postpone its final determination until after a public hearing is held.
Persons with a disability who require an auxiliary aid, service, including TDD users, or other accommodations to seek additional information should contact the Department through the Pennsylvania AT&T Relay Service at (800) 654-5984.
I. NPDES Renewal Applications
Northeast Region: Water Management Program Manager, 2 Public Square, Wilkes-Barre, PA 18711-0790.
NPDES No.
(Type)Facility Name &
AddressCounty &
MunicipalityStream Name
(Watershed #)EPA Waived
Y/N ?PA0063878
(Mun. Sewage)Northeastern Schuylkill Joint Municipal Authority
P. O. Box 170
Barnesville, PA 18214Schuylkill County
Rush TownshipPine Creek
03AY PA0040690
(Minor Sewage)Lakeland School District
1569 Lakeland Drive
Jermyn, PA 18433-3140Scott Township
Lackawanna CountySouth Branch Tunkhannock Creek
4FY PA0060429
(Minor Sewage)Camp Speers--Eljabar YMCA
R. R. 1
Box 89
Dingmans Ferry, PA 18328Delaware Township
Pike CountyUNT to Dingmans Creek
01DY
Southcentral Region: Water Management Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110, (717) 705-4707.
NPDES No.
(Type)Facility Name &
AddressCounty &
MunicipalityStream Name
(Watershed #)EPA Waived
Y/N ?PA0084085
(SEW)Country View Estates MHP
P. O. Box 175
Newville, PA 17421Cumberland County
Upper Frankford TownshipBosler Creek
7BY PA0081345
(SEW)Grier Foundation
c/o Grier School
P. O. Box 308
Tyrone, PA 16686-0308Huntingdon County
Warriors Mark TownshipLittle Juniata River
11-AY
Northcentral Region: Water Management Program Manager, 208 West Third Street, Williamsport, PA 17701.
NPDES No.
(Type)Facility Name &
AddressCounty &
MunicipalityStream Name
(Watershed #)EPA Waived
Y/N ?PA0228770
CAFOBishcroft Farm, LLC
R. D. 1
Box 58
Roaring Branch, PA 17765Tioga County
Liberty TownshipLittle Elk Creek
10AN PA0209651
SewerageColumbia Investment Corp.
6009 Columbia Boulevard
Bloomsburg, PA 17815Main Township
Columbia CountyUNT to Catawissa Creek
5EY
Northwest Region: Water Management Program Manager, 230 Chestnut Street, Meadville, PA 16335-3481.
NPDES No.
(Type)Facility Name &
AddressCounty &
MunicipalityStream Name
(Watershed #)EPA Waived
Y/N ?PA0210358 Patricia C. and Robert G. Gabreski
842 Quaker Hill Road
Warren, PA 16365Glade Township
Warren CountyUNT to Conewango Creek
16-BY
II. Applications for New or Expanded Facility Permits, Renewal of Major Permits and EPA Nonwaived Permit Applications
Southeast Region: Water Management Program Manager, 2 East Main Street, Norristown, PA 19401.
PA0054305, Industrial Waste, SIC 4226, Sunoco Partners Marketing and Terminals, LP, 525 Fritztown Road, Sinking Spring, PA 19608. This existing facility is located in West Whiteland Township, Chester County.
Description of Proposed Activity: Renewal of the NPDES permit for discharge of stormwater runoff by means of an oil/water separator from Sunoco Exton Terminal, a petroleum marketing terminal.
The receiving stream, a UNT to Valley Creek, is in the State Water Plan Watershed 3H and is classified for: CWF, aquatic life, water supply and recreation.
The proposed requirements for Outfall 001 apply to the discharge of stormwater:
Mass (lb/day) Concentration (mg/l) Average Maximum Average Maximum Instantaneous Parameters Monthly Daily Monthly Daily Maximum (mg/l) Total Recoverable Petroleum Hydrocarbons 15 30 Diesel Range Organics, Total Monitor and Report In addition to the effluent limits, the permit contains the following major special conditions:
1. Monitoring and Reporting Requirements.
2. Remedial Measures if Unsatisfactory Effluent.
3. BAT/ELG Reopener.
4. Requirement to Remove Oil from Stormwater.
5. PPC Plan.
6. No Discharge of Untreated or Inadequately Treated Water.
7. Definitions.
8. Hydrostatic Test Water Discharge Requirements.
PA0012891, Sewage, SIC 4952, The Upper Hanover Authority, 1704 Pillsbury Road, East Greenville, PA 18041. This proposed facility is located in Upper Hanover Township, Montgomery County.
Description of Proposed Activity: This application is for renewal of an NPDES permit to discharge treated sewage from The Upper Hanover Authority wastewater treatment plant in Upper Hanover Township, Montgomery County.
The receiving stream Perkiomen Creek is in the State Water Plan Watershed 3E and is classified for TSF. The nearest downstream public water supply intake is for Philadelphia Suburban Water Company, which is located 26.81 miles below this discharge.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.098 mgd:
Mass (lb/day) Concentration (mg/l) Average Average Average Average Instantaneous Parameters Monthly Weekly Monthly Weekly Maximum CBOD5 (5-1 to 10-31) 20 32 25 40 50 Total Suspended Solids 25 37 30 45 60 Ammonia as N (5-1 to 10-31) 4.0 5.0 10.0 (11-1 to 4-30) 12.0 15.0 30.0 Phosphorus as P (4-1 to 10-31) 0.4 0.5 1.0 Total Dissolved Solids 817 1,635
Daily Max1,000 2,000
Daily Max2,500 Fecal Coliform 200 #/100 ml
1,000 #/100 ml
Dissolved Oxygen 3.0 Minimum at all times
pH (Standard Units) Within Limits of 6.0 to 9.0 Standard Units at all times The EPA waiver is in effect.
Other Requirements:
1. Operator Notification.
2. ''Average Weekly'' Definition.
3. Remedial Measures.
4. No Stormwater.
5. Acquiring Necessary Property Rights.
6. Small Stream Discharge.
7. Change in Ownership.
8. Proper Sludge Disposal.
9. Applicable TMDL/WLA Analysis.
10. Certified Operator Requirements.
11. ''Instantaneous Maximum'' Definition.
12. 2/Month Monitoring Requirements.
13. Operation and Maintenance Plan.
14. Fecal Coliform Monitoring Requirements.
15. UV Disinfection.
Northeast Region: Water Management Program Manager, 2 Public Square, Wilkes-Barre, PA 18711-0790.PA-0046388-A1, Sewage, Butler Township, 415 West Butler Drive, Drums, PA 18222. This proposed facility is located in Butler Township, Luzerne County.
Description of Proposed Activity: Increase discharge of treated sewage from 0.6 mgd to 2.2 mgd.
The receiving stream, Nescopeck Creek, is in the State Water Plan Watershed 5D and is classified for: TSF. The nearest downstream public water supply intake for Danville Water Supply is located on Susquehanna River approximately 30 miles below the point of discharge.
The proposed effluent limits for Outfall 001 based on a design flow of 0.6 mgd.
Average Average Instantaneous Parameter Monthly (mg/l) Weekly (mg/l) Maximum (mg/l) CBOD5 25 40 50 Total Suspended Solids 30 45 60 NH3-N (5-1 to 10-31) 12.0 24 Dissolved Oxygen A minimum of 5.0 mg/l at all times.
Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Mean
(10-1 to 4-30) 2,000/100 ml as a Geometric Mean
pH 6.0 to 9.0 Standard Units at all times.
Total Residual Chlorine 1.0 2.0 The proposed effluent limits for Outfall 001 based on a design flow of 2.2 mgd.
Average Average Instantaneous Parameter Monthly (mg/l) Weekly (mg/l) Maximum (mg/l) CBOD5 25 40 50 Total Suspended Solids 30 45 60 NH3-N (5-1 to 10-31) 4.7 9.3 (11-1 to 4-30) 14.0 Dissolved Oxygen A minimum of 5.0 mg/l at all times.
Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Mean (10-1 to 4-30) 2,000/100 ml as a Geometric Mean pH 6.0 to 9.0 Standard Units at all times. Total Residual Chlorine 0.28 0.65 Chesapeake Bay Tributary Strategy Nutrient Requirements
Concentration (mg/l) Mass (lbs) Monthly Monthly Annual Parameter Average Load Load Ammonia-N Report
Report
Report**
Kjeldahl-N Report
Report
Nitrate-Nitrate as N Report Report Total Nitrogen Report
Report
Report Total Phosphorus Report
Report
Report
Net Total Nitrogen Report
40,182 lbs*/yr.
Net Total Phosphorus Report
5,351 lbs*/yr. * This permit contains conditions which authorize the permittee to apply nutrient reduction credits to meet the Net Total Nitrogen and the Net Total Phosphorus effluent mass limits, under the Department of Environmental Protection's (Department) Trading of Nutrients and Sediment Reduction Credits Policy and Guidelines (Document No. 392-0900-001, December 30, 2006). The condition includes the requirement to report the application of these credits in Supplemental Discharge Monitoring Reports (DMRs) submitted to the Department.
* The compliance date for Net Total Nitrogen and Net Total Phosphorus will begin on October 1, 2010. Since these reporting requirements are annual loads, the reporting on compliance with the annual limitations will be required to be reported on the Supplemental DMR--Annual Nutrient Summary by November 28, 2011. This facility is required to monitor and report for Net Total Nitrogen and Net Total Phosphorus from the effective date of the permit until September 30, 2010.
** Total Annual Ammonia Load will be required to be reported on the Supplemental DMR--Annual Nutrient Summary by November 28, 2011.
In addition to the effluent limits, the permit contains the following major special conditions:
1. Whole Effluent Toxicity Testing Monitoring.
Southcentral Region: Water Management Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110, (717) 705-4707.Application No. PA 0020478, Sewage, Bloomfield Borough, P. O. Box 144, New Bloomfield, PA 17068. This facility is located in Bloomfield Borough, Perry County.
Description of activity: The application is for renewal of an NPDES permit for an existing discharge of treated sewage.
The receiving stream, a UNT to Trout Run, is in Watershed 7-A, and classified for CWF, water supply, recreation and fish consumption. The nearest downstream public water supply intake for United Water Company is located on the Susquehanna River, approximately 18.9 miles downstream. The discharge is not expected to affect the water supply.
The proposed effluent limits for Outfall 001 for a design flow of 0.25 mgd are:
Average Average Instantaneous Parameter Monthly (mg/l) Weekly (mg/l) Maximum (mg/l) CBOD5 25 40 50 Total Suspended Solids 30 45 60 NH3-N (5-1 to 10-31) 3.5 7.0 (11-1 to 4-30) 10.5 21 Total Zinc 0.019 0.047 Dissolved Oxygen Minimum of 5.0 at all times pH From 6.0 to 9.0 inclusive
Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Average (10-1 to 4-30) 2,000/100 ml as a Geometric Average
Chesapeake Bay Requirements
Concentration (mg/l) Mass (lbs) Parameter Monthly Average Monthly Annual Ammonia-N Report
Kjeldahl-N Report Nitrate-Nitrite as N Report
Total Nitrogen Report
Total Phosphorus Report Persons may make an appointment to review the Department of Environmental Protection's files on this case by calling the file review coordinator at (717) 705-4732.
The EPA waiver is in effect.
Application No. PA 0010502, Industrial Waste, SIC Code 3489, 3471 and 3483, Letterkenny Army Depot, One Overcash Avenue, Building 14, Chambersburg, PA 17201-4150. This facility is located in Greene Township, Franklin County.
Description of activity: The application is for renewal of an NPDES permit for existing discharge of treated industrial waste.
The receiving stream, Rowe Run (Outfalls 001 and S02), is in Watershed 7-B, and classified for CWF, water supply, recreation and fish consumption. The nearest downstream public water supply intake is Carlisle Borough located on the Conodoguinet Creek, approximately 44.9 miles downstream. The discharge is not expected to affect the water supply.
The receiving stream, a UNT to Conococheague Creek (Outfall S01), is in Watershed 13-C, and classified for CWF, water supply, recreation and fish consumption. The nearest downstream public water supply intake is Hagerstown Borough, MD located on the Conococheague Creek, approximately 62 miles downstream. The discharge is not expected to affect the water supply.
The receiving stream, Rocky Spring Branch (Outfall S03), is in Watershed 13-C, and classified for TSF, water supply, recreation and fish consumption. The nearest downstream public water supply intake is Hagerstown Borough, MD located on the Conococheague Creek, approximately 60 miles downstream. The discharge is not expected to affect the water supply.
The proposed effluent limits for Outfall 001 based on a design flow of 0.290 mgd are:
Mass (lb/day) Concentration (mg/l) Average Maximum Average Maximum Instantaneous Parameter Monthly Daily Monthly Daily Maximum pH (Standard Units) XXX
XXX
6.0 (Minimum)
XXX
9.0 Oil and Grease 36 72 15 30 30 CBOD5 48 97 20 40 50 Total Suspended Solids 24 48 10 20 25 Total Phosphorus 4.8 9.7 2.0 4.0 5.0 Total Chromium 4.13 6.70 1.71 2.77 4.25 Total Lead 0.10 0.20 0.042 0.84 0.105 Total Nickel 1.06 2.12 0.44 0.88 1.10 Total Cyanide Monitor and Report
Monitor and Report
0.65 1.20 1.62 Total Silver 0.14 0.27 0.57 0.114 0.142 Total Zinc 1.54 3.09 0.64 1.28 1.60 Total Toxic Organics XXX
XXX
XXX
2.13 XXX
Total Cadmium 0.0048 0.009 0.002 0.004 0.005 Total Copper 0.19 0.38 0.079 0.158 0.197 Interim Bis (2-Ethylhexyl Phthalate (PED to ) Monitor and Report
Monitor and Report
Monitor and Report
Monitor and Report
XXX
Final Bis (2-Ethylhexyl) Phthalate ( to expiration) 0.077 0.154 0.032 0.064 0.080 The proposed effluent limits for Outfalls S01 and S03 discharging stormwater are:
Concentration (mg/l) Average Maximum Instantaneous Parameter Monthly Daily Maximum CBOD5 XXX XXX Monitor and Report
Chemical Oxygen Demand XXX XXX Monitor and Report
Total Suspended Solids XXX XXX Monitor and Report
Total Phosphorus XXX XXX Monitor and Report
Total Kjeldahl Nitrogen XXX XXX Monitor and Report
Total Iron XXX XXX Monitor and Report
Oil and Grease XXX XXX Monitor and Report
pH (Standard Units) XXX XXX Monitor and Report The proposed effluent limits for Outfall S02 discharging stormwater are:
Concentration (mg/l) Average Maximum Instantaneous Parameter Monthly Daily Maximum CBOD5 XXX XXX Monitor and Report
Chemical Oxygen Demand XXX XXX Monitor and Report
Total Suspended Solids XXX XXX Monitor and Report
Total Phosphorus XXX XXX Monitor and Report Total Kjeldahl Nitrogen XXX XXX Monitor and Report
Total Iron XXX XXX Monitor and Report
Oil and Grease XXX XXX Monitor and Report
pH (Standard Units) XXX XXX Monitor and Report
Total Cadmium XXX XXX Monitor and Report
Total Chromium XXX XXX Monitor and Report
Total Copper XXX XXX Monitor and Report
Total Lead XXX XXX Monitor and Report
Total Nickel XXX XXX Monitor and Report
Total Silver XXX XXX Monitor and Report
Total Zinc XXX XXX Monitor and Report
Total Cyanide XXX XXX Monitor and Report
TTO XXX XXX Monitor and Report
Persons may make an appointment to review the Department of Environmental Protection's files on this case by calling the file review coordinator at (717) 705-4732.
The EPA waiver is not in effect.
Southwest Regional Office: Regional Manager, Water Management, 400 Waterfront Drive, Pittsburgh, PA 15222-4745, (412) 442-4000.PA0094382, Sewage, Greensburg Salem School District, 1 Academy Hill Place, Greensburg, PA 15601. This application is for renewal of an NPDES permit to discharge treated sewage from Metzgar Elementary School STP in Salem Township, Westmoreland County.
The following effluent limitations are proposed for discharge to the receiving waters, known as Loyalhanna Lake, which are classified as a WWF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the Municipal Authority of Buffalo Township.
Outfall 001: existing discharge, design flow of 0.005 mgd.
Concentration (mg/l) Average Average Maximum Instantaneous Parameter Monthly Weekly Daily Maximum CBOD5 25 50 Suspended Solids 30 60 Ammonia Nitrogen 25 50 Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Mean
(10-1 to 4-30) 2,000/100 ml as a Geometric Mean
Total Residual Chlorine 1.4 3.3 Dissolved Oxygen not less than 3.0 mg/l
pH not less than 6.0 nor greater than 9.0
The EPA waiver is in effect.
PA0032247, Sewage, Department of Conservation and Natural Resources, Bureau of State Parks, 1454 Laurel Hill Park Road, Somerset, PA 15501-5629. This application is for renewal of an NPDES permit to discharge treated sewage from Laurel Hill State Park STP in Middlecreek Township, Somerset County.
The following effluent limitations are proposed for discharge to the receiving waters, known as Laurel Hill Creek, which are classified as a HQ-CWF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the Ohiopyle Borough Municipal Waterworks.
Outfall 001: existing discharge, design flow of 0.19 mgd.
Concentration (mg/l) Average Average Maximum Instantaneous Parameter Monthly Weekly Daily Maximum CBOD5 15 30 Suspended Solids 30 60 Ammonia Nitrogen (5-1 to 10-31) 3.0 6.0 (11-1 to 4-30) 9.0 18.0 Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Mean
(10-1 to 4-30) 2,000/100 ml as a Geometric Mean
Total Residual Chlorine 1.0 3.3 Dissolved Oxygen not less than 5.0 mg/l
pH not less than 6.0 nor greater than 9.0
The EPA waiver is in effect.
PA0090981, Sewage, German Township, R. D. 1, Box 287, McClellandtown, PA 15458-0287. This application is for renewal of an NPDES permit to discharge treated sewage from Footedale STP in German Township, Fayette County.
The following effluent limitations are proposed for discharge to the receiving waters, known as UNT of Dunlap Creek, which are classified as a WWF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the Brownsville Water Company.
Outfall 001: existing discharge, design flow of 0.085 mgd.
Concentration (mg/l) Average Average Maximum Instantaneous Parameter Monthly Weekly Daily Maximum CBOD5 25 50 Suspended Solids 30 60 Ammonia Nitrogen (5-1 to 10-31) 5.5 11.0 (11-1 to 4-30) 16.5 33.0 Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Mean
(10-1 to 4-30) 2,000/100 ml as a Geometric Mean
Total Residual Chlorine 1.3 3.1 pH not less than 6.0 nor greater than 9.0
The EPA waiver is in effect.
PA0217921, Sewage, Indiana Investments, Inc., R. D. 2, Box 305, Shelocta, PA 15774. This application is for renewal of an NPDES permit to discharge treated sewage from Indiana Investments STP in Armstrong Township, Indiana County.
The following effluent limitations are proposed for discharge to the receiving waters, known as Walker Run, which are classified as a CWF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the Buffalo Township Municipal Authority-Freeport.
Outfall 001: existing discharge, design flow of 0.00625 mgd.
Concentration (mg/l) Average Average Maximum Instantaneous Parameter Monthly Weekly Daily Maximum CBOD5 25 50 Suspended Solids 30 60 Ammonia Nitrogen (5-1 to 10-31) 22.0 44.0 (11-1 to 4-30) Monitor and Report
Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Mean
(10-1 to 4-30) 2,000/100 ml as a Geometric Mean
Total Residual Chlorine 1.4 3.3 pH not less than 6.0 nor greater than 9.0 The EPA waiver is in effect.
PA0098060, Sewage, Eugene J. Smith, Jr., 106 Chrissy's Crossing, Fombell, PA 16123. This application is for renewal of an NPDES permit to discharge treated sewage from Smithwind Mobile Home Park STP in Franklin Township, Beaver County.
The following effluent limitations are proposed for discharge to the receiving waters, known as UNT of Slippery Rock Creek, which are classified as a CWF with existing and/or potential uses for aquatic life, water supply and recreation. The first downstream potable water supply intake from this facility is the PA American Water Company, Ellwood District, on Slippery Rock Creek.
Outfall 001: existing discharge, design flow of 0.0022 mgd.
Concentration (mg/l) Average Average Maximum Instantaneous Parameter Monthly Weekly Daily Maximum CBOD5 25 50 Suspended Solids 30 60 Ammonia Nitrogen (5-1 to 10-31) 2.5 5.0 (11-1 to 4-30) 6.0 12.0 Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Mean
(10-1 to 4-30) 2,000/100 ml as a Geometric Mean
Total Residual Chlorine 0.06 0.14 Dissolved Oxygen not less than 6.0 mg/l
pH not less than 6.0 nor greater than 9.0
The EPA waiver is in effect.
Northwest Region: Water Management Program Manager, 230 Chestnut Street, Meadville, PA 16335-3481.PA0036994-Amendment No. 1, Sewage, Borough of Pleasantville, 114 West State Street, P. O. Box 150, Pleasantville, PA 16341. This proposed facility is located in Pleasantville Borough, Venango County.
Description of Proposed Activity: Amendment of an NPDES Permit for an existing discharge of treated sewage.
For the purpose of evaluating effluent requirements for TDS, NO2-NO3, fluoride, phenolics, sulfate and chloride, the existing/proposed downstream potable water supply, considered during the evaluation is the Parker City intake is located on the Allegheny River and is approximately 63 miles below point of discharge.
The receiving stream, West Pithole Creek, is in Watershed 16-E and classified for: CWF, aquatic life, water supply and recreation.
The proposed effluent limits for Outfall 001 are based on a design flow of 0.31 mgd.
Interim Limits
Loadings Concentrations Average Average Average Average Instantaneous Parameters Monthly (lb/day) Weekly (lb/day) Monthly (mg/l) Weekly (mg/l) Maximum (mg/l) Flow (mgd) XX CBOD5 64 103 25 40 50 Total Suspended Solids 77 116 30 45 60 NH3-N (5-1 to 10-31) 5 2 4 (11-1 to 4-30) 15 6 12 Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Average
(10-1 to 4-30) 2,000/100 ml as a Geometric Average
Total Residual Chlorine 0.03 0.1 Dissolved Oxygen minimum of 6 mg/l at all times
Phosphorus as ''P'' 4 XX Total Nitrogen 12 XX pH 6.0 to 9.0 Standard Units at all times
The proposed effluent limits for Outfall 001 are based on a design flow of 0.4 mgd.
Final Limits
Loadings Concentrations Average Average Average Average Instantaneous Parameters Monthly (lb/day) Weekly (lb/day) Monthly (mg/l) Weekly (mg/l) Maximum (mg/l) Flow (mgd) XX CBOD5 33 50 10 15 20 Total Suspended Solids 33 50 10 15 20 NH3-N (5-1 to 10-31) 6.5 2 4 (11-1 to 4-30) 20 6 10 Fecal Coliform (5-1 to 9-30) 200/100 ml as a Geometric Average
(10-1 to 4-30) 2,000/100 ml as a Geometric Average
Dissolved Oxygen minimum of 6 mg/l at all times
Phosphorus as ''P'' 1.5 0.5 Total Nitrogen 12 3.6 pH 6.0 to 9.0 Standard Units at all times XX--Monitor and report on monthly DMRs.
The EPA waiver is in effect.
III. WQM Industrial Waste and Sewerage Applications under The Clean Streams Law (35 P. S. §§ 691.1--691.1001)
Southeast Region: Water Management Program Manager, 2 East Main Street, Norristown, PA 19401.
WQM Permit No. 4609401, Sewerage, Pottstown Borough Authority, 100 East High Street, Pottstown, PA 19464. This proposed facility is located in Pottstown Borough, Montgomery County.
Description of Action/Activity: New 30" sewer to replace 100 (+/-) feet of existing 21" sewer from Beech Street south to Hanover Street
WQM Permit No. 4609402, Sewerage, Upper Pottsgrove Township, 1409 Farmington Avenue, Pottstown, PA 19464. This proposed facility is located in Upper Pottsgrove Township, Montgomery County.
Description of Action/Activity: Construction and operation of a sewage pump station.
Northeast Region: Water Management Program Manager, 2 Public Square, Wilkes-Barre, PA 18711-0790.
WQM Permit No. 4809401, Sewerage, EPI, LLC/EAST P I, LLC, 6831 East 32nd Street, Indianapolis, IN 46226. This proposed facility is located in Lower Nazareth and Bethlehem Townships, Northampton County.
Description of Proposed Action/Activity: This project is for the construction of a sewage treatment plant and spray irrigation system with a design capacity of 7,500 gpd.
WQM Permit No. 1308404, Sewerage, Big Boulder Corporation, P. O. Box 707, Blakeslee, PA 18610-0707. This proposed facility is located in Kidder Township, Carbon County.
Description of Proposed Action/Activity: This project involves treatment plant modifications and construction of an additional soil absorption bed. The treatment plant modifications include installation of a second flocculator and tray settler, replacement of the existing chlorine disinfection unit with an ultraviolet disinfection system and conversion of the existing chlorine contact tank to an equalization tank.
Southcentral Region: Water Management Program Manager, 909 Elmerton Avenue, Harrisburg, PA 17110, (717) 705-4707.
WQM Permit No. 0509401, Sewerage, David Graham, 117 Valentine Acres Road, Clearville, PA 15535. This proposed facility is located in Southampton Township, Bedford County.
Description of Proposed Action/Activity: Seeking approval for the construction/operation of a small flow sewage treatment system to serve their single family residence on Valentine Acres Road.
Northwest Region: Water Management Program Manager, 230 Chestnut Street, Meadville, PA 16335-3481.
WQM Permit No. 6109401, Sewerage, Matric Limited Inc., 2099 Hill City Road, Seneca, PA 16345 This proposed facility is located in Cranberry Township, Venango County.
Description of Proposed Action/Activity: Construction of a 6,800 gpd extended aeration package plant to replace a malfunctioning onlot system to treat sewage from their facility that currently employs 300+ employees.
IV. NPDES Applications for Stormwater Discharges from Municipal Separate Storm Sewer Systems (MS4)
V. Applications for NPDES Wavier Stormwater Discharges from Municipal Separate Storm Sewer Systems (MS4)
VI. NPDES Individual Permit Applications for Discharges of Stormwater Associated with Construction Activities
Southeast Region: Water Management Program Manager, 2 East Main Street, Norristown, PA 19401.
NPDES
Permit No.Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAS10-
G466-ROrleans Homebuilders, Inc.
333 Street Road
Suite 101
Bensalem, PA 19020Chester West Bradford Township Broad Run
EV
West Branch Brandywine Creek
WWF-MF
PAI01
1505043-RThe Hankin Group
707 Eagleview Boulevard
Exton, PA 19341Chester Uwchlan Township Shamona Creek
HQ-TSFPAI01
1509001IHM Immaculata--Villa Maria
House of Studies
1140 King Road
Immaculata, PA 19345Chester East Whiteland Township UNT Ridley Creek
HQ-TSFPAI01
1509002Phoenix Property Group
100 French Creek Parkway
Phoenixville, PA 19460Chester Phoenixville
BoroughFrench Creek/Schuylkill River
TSFPAI01
1509003Lanchester Properties, LLC
155 Ponds View Drive
Oxford, PA 19363Chester East Nottingham Township West Branch Big Elk Creek
HQ-TSF-MFPAI01
1509004BK Campbell, Inc.
402 Bayard Road
Suite 101
Kennett Square, PA 19348Chester Lower Oxford Township West Branch Big Elk Creek
HQ-TSF-MFNortheast Region: Watershed Management Program Manager, 2 Public Square, Wilkes-Barre, PA 18711-0790.
Monroe County Conservation District: 8050 Running Valley Road, Stroudsburg, PA 18360, (570) 629-3060.
NPDES
Permit No.Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAI024503001R James P. Ertle
R. R. 2
Box 30
Kunkletown, PA 18058
and
Northeast Site Contractors
4499 Route 611
Suite C
Stroudsburg, PA 18360Monroe Hamilton and
Stroud TownshipsPocono Creek
HQ-CWFLehigh County Conservation District: Lehigh Agriculture Center, Suite 102, 4184 Dorney Park Road, Allentown, PA 18104, (610) 391-9583.
NPDES
Permit No.Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAI023909004 Christopher Fencel
Cedar--Trexler Hamilton, LLC
3307 Trindle Road
Camp Hill, PA 17011Lehigh Lower Macungie
and Upper Macungie TownshipsUNT to Iron Run
HQ-CWFPAI023909005 Mark Leuthe
Robyn Realty Co.
3906 Mountain View Drive
Danielsville, PA 18038Lehigh Lowhill Township UNT to Jordan Creek
HQ-CWF, MF
Lehigh River
WWFPAI023909002 Susanne Meixsell
Northwestern Lehigh School District
6493 Route 309
New Tripoli, PA 18066Lehigh Heidelberg and Lynn Townships UNT of Jordan Creek
HQ-CWF, MF
School Creek
EVPAI023909006 Pravin Desai Yamunaji Corp.
7471 Keebler Way
Allentown, PA 18106Lehigh Upper Macungie Township Iron Run, Spring Creek
Little Lehigh Creek
HQ-CWFNorthcentral Region: Water Management Program Manager, 208 West Third Street, Williamsport, PA 17701.
Centre County Conservation District: 414 Holmes Avenue, Suite 4, Bellefonte, PA 16823, (814) 355-6817.
NPDES
Permit No.Applicant Name &
AddressCounty Municipality Receiving
Water/UsePAI041409001 John Elnitski
Bellefonte Airport
225 Snowbird Lane
Bellefonte, PA 16823Centre Benner Township UNT to Buffalo Run
CWF
VII. List of NOIs for NPDES and/or Other General Permit Types
PAG-12 Concentrated Animal Feeding Operations (CAFOs) PAG-13 Stormwater Discharges from Municipal Separate Storm Sewer Systems (MS4)
[Continued on next Web Page]
No part of the information on this site may be reproduced for profit or sold for profit.This material has been drawn directly from the official Pennsylvania Bulletin full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.