4 Pa. Code § 67c.5. Nursing Mothers Room design requirements.

§ 67c.5. Nursing Mothers Room design requirements.

 All Nursing Mothers Rooms created under this chapter must:

   (1)  Be in a location that complies with the Americans with Disabilities Act of 1990 (ADA) (42 U.S.C.A. § §  12101-12213). All accessories, equipment, furniture and casework shall be provided and installed to comply with ADA requirements, including but not limited to accessibility clearances and regulations.

   (2)  Have a minimum square footage of 80 net useable square feet.

   (3)  Have a privacy latch or locking door hardware, or both so that the door can be locked from the inside.

   (4)  Provide visual privacy to the space by modifying or covering windows, sidelights and doors.

   (5)  Provide sound privacy to the space to minimize sound transmission into adjacent spaces, including using sound attenuation insulation if possible.

   (6)  Include a chair and table, countertop or desk. The chair must be upholstered, cushioned, have armrests, a high back and be of standard seating height.

   (7)  Provide at least one electrical duplex outlet next to where the individual will be seated.

   (8)  Contain a waste receptacle.

   (9)  Meet standard office level illumination and ventilation requirements.

   (10)  Not be a restroom, toilet stall, storage room or janitor’s closet.