25 Pa. Code § 109.1002. MCLs, MRDLs or treatment techniques.

§ 109.1002. MCLs, MRDLs or treatment techniques.

 (a)  Bottled water and vended water systems, retail water facilities and bulk water hauling systems shall supply drinking water that complies with the MCLs, MRDLs and treatment technique requirements under § §  109.202 and 109.203 (relating to State MCLs, MRDLs and treatment technique requirements; and unregulated contaminants). Bottled water systems, vended water systems, retail water facilities and bulk water hauling systems using surface water or GUDI sources shall comply with the requirements in §  109.204 (relating to disinfection profiling and benchmarking). Bottled water systems, vended water systems, retail water facilities and bulk water hauling systems shall provide continuous disinfection for groundwater sources. Water for bottling labeled as mineral water under §  109.1007 (relating to labeling requirements for bottled water systems, vended water systems and retail water facilities) shall comply with the MCLs except that mineral water may exceed the MCL for total dissolved solids.

 (b)  Bottled water and vended water systems, retail water facilities and bulk water hauling systems shall supply drinking water that contains no more than 0.005 mg/L of lead and no more than 1.0 mg/L copper.

 (c)  Bottled water and vended water systems, retail water facilities and bulk water hauling systems shall comply with the treatment technique requirements under Subchapter L (relating to long-term 2 enhanced surface water treatment rule).

 (d)  Bottled water and vended water systems, retail water facilities and bulk water hauling systems shall comply with Subchapter M (relating to additional requirements for groundwater sources). For the purpose of determining compliance with Subchapter M, bottled water and vended systems, retail water facilities and bulk water hauling systems using groundwater sources shall comply with standards pertaining to noncommunity groundwater systems.

Authority

   The provisions of this §  109.1002 amended under section 4 of the Pennsylvania Safe Drinking Water Act (35 P.S. §  721.4); and section 1920-A of The Administrative Code of 1929 (71 P.S. §  510-20).

Source

   The provisions of this §  109.1002 adopted May 15, 1992, effective May 16, 1992, 22 Pa.B. 2621; amended October 7, 1994, effective October 8, 1994, 24 Pa.B. 5175; amended July 20, 2001, effective July 21, 2001, 31 Pa.B. 3895; amended December 24, 2009, effective December 26, 2009, 39 Pa.B. 7279; amended April 27, 2018, effective April 28, 2018, 48 Pa.B. 2509. Immediately preceding text appears at serial pages (383489) to (383490).

Cross References

   This section cited in 25 Pa. Code §  109.1005 (relating to permit requirements); 25 Pa. Code §  109.1006 (relating to design and construction standards); and 25 Pa. Code §  109.1009 (relating to system operational requirements).