Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 1032 (February 24, 2024).

34 Pa. Code § 14a.108. Fire control.

§ 14a.108. Fire control.

 (a)  At least two properly maintained 20BC fire extinguishers shall be located within 75 feet of the loading rack. Additional fire protection equipment may be required by the fire marshal if a tank of more than 50,000 gallons individual capacity contains class I liquid.

 (b)  At remote crude storage and pumping areas a properly maintained 20BC fire extinguisher shall be available during those periods of time that the tanks or related equipment are being attended or utilized.

Source

   The provisions of this §  3.108 amended June 22, 1984, effective June 18, 1984, 14 Pa.B. 2131; transferred from 37 Pa. Code and renumbered as 34 Pa. Code §  14a.108, February 28, 2014, effective March 1, 2014, 44 Pa.B. 1233. Immediately preceding text appears at serial pages (259944) to (259945).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.