34 Pa. Code § 14a.12. Prevention of overfilling of tanks.

§ 14a.12. Prevention of overfilling of tanks.

 Tanks receiving transfer of flammable or combustible liquid from mainline pipelines or marine vessels shall be:

 (1)  Gauged at frequent intervals while receiving transfer of product, and communications maintained with mainline pipeline or marine personnel so that flow can be promptly shut down or diverted;

 (2)  Equipped with an independent high level alarm located where personnel are on duty during the transfer and can promptly arrange for flow stoppage or diversion; or

 (3)  Equipped with an independent high level alarm system that will automatically shut down or divert flow.

Source

   The provisions of this §  13.12 adopted June 22, 1984, effective June 18, 1984, 14 Pa.B. 2131; transferred from 37 Pa. Code and renumbered as 34 Pa. Code §  14a.12, February 28, 2014, effective March 1, 2014, 44 Pa.B. 1233. Immediately preceding text appears at serial page (259920).