Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 1032 (February 24, 2024).

34 Pa. Code § 14a.34. Venting.

§ 14a.34. Venting.

 Tanks shall have vent openings and vent pipes of sufficient size to prevent abnormal pressure in the tank during filling. Vent pipes shall terminate outside of buildings, higher than the fill pipe opening, and above normal snow accumulation. All domestic fuel tank installations shall be equipped with a signal alarm to prevent overflow. Where tanks are filled by the use of a pump through tight connection, a vent pipe not less in size than the discharge of the pump shall be used. Under no circumstances shall the vent pipe diameter be less than 1¼ inches nominal inside diameter.

Source

   The provisions of this §  13.34 amended June 22, 1984, effective June 18, 1984, 14 Pa.B. 2131; transferred from 37 Pa. Code and renumbered as 34 Pa. Code §  14a.34, February 28, 2014, effective March 1, 2014, 44 Pa.B. 1233. Immediately preceding text appears at serial page (259930).

Cross References

   This section cited in 34 Pa. Code §  14a.31 (relating to scope); and 34 Pa. Code §  14a.161 (relating to general provisions).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.