Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 1032 (February 24, 2024).

34 Pa. Code § 3a.167. Hot water/steam heat exchangers.

§ 3a.167. Hot water/steam heat exchangers.

 (a)  Heat exchangers must be manufactured under the ASME Code.

 (b)  Heat exchangers must have adequate over-pressure protection to protect both systems.

 (c)  Heat exchangers used for domestic hot water supply must have a high temperature limit switch designed not to exceed 210°F.

 (d)  Inspection of hot water/steam heat exchangers shall be performed in accordance with §  3a.111(8) (relating to field inspections).

Cross References

   This section cited in 34 Pa. Code §  3a.3 (relating to scope).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.