25 Pa. Code § 285.122. Storage tanks.

§ 285.122. Storage tanks.

 (a)  Municipal waste storage tanks shall have sufficient shell strength to ensure that they do not collapse or rupture. Municipal waste may not be placed in a tank if the waste could cause the tank or its inner liner to rupture, leak, corrode or otherwise fail.

 (b)  A person or municipality that stores municipal waste in a tank shall inspect the tank during construction or installation for uniformity, damage and imperfections.

 (c)  If there is evidence of failure of a municipal waste storage tank, the tank shall be immediately removed from service. A tank may not be restored to service unless it has been repaired. The repairs shall be supervised by a registered professional engineer and certified, in writing, to the Department, unless otherwise approved by the Department.

 (d)  A person or municipality that maintains an uncovered municipal waste storage tank shall provide at least 2 feet of freeboard unless the tank is equipped with one of the following:

   (1)  A secondary containment system.

   (2)  An automatic feed cutoff system or an overflow warning system and an overflow device to a standby tank with a capacity equal to or exceeding the volume of the top 2 feet of the uncovered tank.

 (e)  Subsurface tanks used for liquid waste storage shall be hydrostatically tested annually and when there is evidence of a leak. Other methods of tank testing may be approved by the Department, in writing.

 (f)  A person or municipality that stores liquid municipal waste in aboveground tanks or partially aboveground tanks shall build and maintain a containment structure which is designed and located so that it is capable of holding a volume that does the following:

   (1)  Equals or exceeds the largest aboveground tank volume.

   (2)  Has reasonable allowance for precipitation based on local weather conditions.

 (g)  A person or municipality storing municipal waste in an enclosed tank utilizing a continuous or direct-feed mechanism shall maintain an automatic feed cutoff system or an overflow warning system.

Cross References

   This section cited in 25 Pa. Code §  273.275 (relating to leachate collection and storage); 25 Pa. Code §  277.275 (relating to leachate collection and storage); and 25 Pa. Code §  285.101 (relating to scope).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.