Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 488 (January 27, 2024).

34 Pa. Code § 35.112. Wiring.

§ 35.112. Wiring.

 Except for the purpose of cleaning or making repairs or other adjustments, all electrical wiring in booths or room booths shall be of a permanent character. Portable lamps shall be incased in vapor-proof globes with suitable mechanical guards. Permanent electrical wiring in booths or room booths shall be installed in rigid or flexible metal conduits or raceways. All wiring within 30 feet of the face of the booth, in rooms in which booths are located, shall be installed in rigid or flexible metal conduits or raceways.



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.