34 Pa. Code § 56.52. Required.

§ 56.52. Required.

 An automatic fire alarm system shall be installed in all facilities.

   (1)  Detection Devices shall be listed as meeting U. L. 217, 1980 Edition. A minimum of one automatic detection device shall be provided on each floor including basement. One automatic detection device shall be located in a common area such as a hall, corridor, or similar area. A detection device shall be located at the top or bottom of each stair. This device may satisfy the requirement for a minimum of one detection device on each floor. See Diagram A for suggested locations of detection devices.

Diagram A

DIAGRAM A


   (2)  The top of wall mounted detection devices shall be 4 to 12 inches from the ceiling.

   (3)  Ceiling mounted detection devices shall be located close to the center of the common area, but in no case closer than 6 inches from the wall.

   (4)  An automatic detection device shall be located outside each sleeping room or area. See Diagram B for suggested locations of detection devices.

Diagram B

   (5)  The automatic detection devices shall be interconnected so all alarm devices sound if any is activated.