Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 488 (January 27, 2024).

25 Pa. Code § 145.213. Supplemental monitoring, recordkeeping and reporting requirements for gross electrical output and useful thermal energy for units subject to 40 CFR 96.170—96.175.

§ 145.213. Supplemental monitoring, recordkeeping and reporting requirements for gross electrical output and useful thermal energy for units subject to 40 CFR 96.170—96.175.

 (a)  By January 1, 2009, or by the date of commencing commercial operation, whichever is later, the owner or operator of the CAIR NOx unit shall install, calibrate, maintain and operate a wattmeter, measure gross electrical output in megawatt-hours on a continuous basis and record the output of the wattmeter. If a generator is served by two or more units, the information to determine the heat input of each unit for that control period shall also be recorded, so as to allow each unit’s share of the gross electrical output to be determined. If heat input data are used, the owner or operator shall comply with the applicable provisions of 40 CFR Part 75 (relating to continuous emission monitoring).

 (b)  By September 1, 2008, for a CAIR NOx unit that is a cogeneration unit, and for a CAIR NOx unit with cogeneration capabilities, the owner or operator shall install, calibrate, maintain and operate meters for steam flow in lbs/hr, temperature in degrees Fahrenheit, and pressure in PSI, to measure and record the useful thermal energy that is produced, in mmBtu/hr, on a continuous basis. The owner or operator of a CAIR NOx unit that produces useful thermal energy but uses an energy transfer medium other than steam, such as hot water or glycol, shall install, calibrate, maintain and operate the necessary meters to measure and record the data necessary to express the useful thermal energy produced, in mmBtu/hr, on a continuous basis. If the unit ceases to produce useful thermal energy, the owner or operator may cease operation of the meters, but operation of the meters shall be resumed if the unit resumes production of useful thermal energy.

 (c)  Beginning with 2009, the designated representative of the unit shall submit to the Department an annual report showing monthly gross electrical output and monthly useful thermal energy from the unit. The report is due by January 31 for the preceding calendar year.

 (d)  The owner or operator of a CAIR NOx unit shall maintain onsite the monitoring plan detailing the monitoring system and maintenance of the monitoring system, including quality assurance activities. The owner or operator of a CAIR NOx unit shall retain the monitoring plan for at least 5 years from the date that it is replaced by a new or revised monitoring plan. The owner or operator of a CAIR NOx unit shall provide the Department with a written copy of the monitoring plan by January 1, 2009, and thereafter within 3 calendar months of making updates to the plan.

 (e)  The owner or operator of a CAIR NOx unit shall retain records for at least 5 years from the date the record is created or the data collected as required by subsections (a) and (b), and the reports submitted to the Department and the EPA in accordance with subsections (c) and (d).



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.