Pennsylvania Code & Bulletin
COMMONWEALTH OF PENNSYLVANIA

• No statutes or acts will be found at this website.

The Pennsylvania Code website reflects the Pennsylvania Code changes effective through 54 Pa.B. 1032 (February 24, 2024).

34 Pa. Code § 23.121. Fire protection devices.

CLASS II AND III PLANTS—ADDITIONAL REQUIREMENTS


§ 23.121. Fire protection devices.

 (a)  As a means of fire extinguishing in any drycleaning, dyeing, tumbler or drying room, the rooms shall be equipped with steam pipes which shall be separate from and other than the pipes used for heating or power and shall be located near the ceiling. In these pipes there shall be not less than two openings for each room, all of which shall point toward the ceiling. The steam supply for these pipes shall be continually available for service while the plant is in operation and shall be sufficient to completely fill the room space in less than one minute. An outside screw and yoke valve shall be placed in the steam service lines or other lines outside of these rooms, which shall be accessible for operation in case of fire.

 (b)  An approved system, using a fire detergent chemical or gas or an approved sprinkler system may be installed in lieu of a steam extinguishing system.

 (c)  A steam fire protection system shall be extended and connected to all washers and tumblers so that the fire extinguishing agent may be admitted to the interior of the machine. The equipment shall provide a steam jet not less than 3/4 inch from a continuously available steam supply at a pressure not less than 15 pounds per square inch.



No part of the information on this site may be reproduced for profit or sold for profit.


This material has been drawn directly from the official Pennsylvania Code full text database. Due to the limitations of HTML or differences in display capabilities of different browsers, this version may differ slightly from the official printed version.