34 Pa. Code § 39.106. Isolating live parts by elevation.

§ 39.106. Isolating live parts by elevation.

 Current-carrying parts need not be guarded if they are maintained at the following distances above the floors which may be occupied by persons:

Voltage of ConductorsElevation (in feet)
300—750 7
750—2,500 7
2,500—7,500 8
7,500—30,000 9
30,000—70,00010
70,000—100,00012
Over 100,00014